Phone:+86-0755-33896688
FAX: +86-0755-33896824
Address:IBE Industrial Building,No.15,Guotai Road,The first industry zone of Tangtou,Shiyan Town,Bao'an District, 518108,Shenzhen,Guangdong Province,China
|
|
|
|
|
|
|
 |
 |
|
|
| Name: |
DSSD1353/DTSD1353 Three phase static multi-function energy meter DSSD1353/DTSD1353
|
【Order Info】
|
| Description: |
Functions and Features
- Measurement of positive/negative active/reactive energy and demand, power consumption and demand in each tariff
- Measurement of four quadrant reactive energy
- 4 tariff, 10 day time period, 5 day time tables, 4 time zones and 12 public holidays can be programmable
- Display meter data by LCD, optional backlight display
- Scroll-display, the parameters(not exceed 32 items), time and sequence of scroll-display can be set randomly
- Real-time measurement of voltage, current, power factor and current frequency in each phase
- Record the events of voltage loss, current loss, voltage qualified rate, power cut and on, programming, demand reset, broadcast time checking etc.
- With energy pulse and clock testing output interface
- Infrared remote during power break and awakening by pressing button, infrared remote meter-reading when power break can also be realized
- Infrared and RS485 communication interface
- Fault alarming
- Record the result of current inspection without voltage.
|
Items |
Technical Parameters |
|
Rated voltage |
3*220/380V, 3*57.7/100V (Three phase 4 wire);3*100V(Three phase 3 wire) |
|
Basic current |
0.5(2)A、1(2)A、1.5(6)A、3(6)A、5(20)A、10(40)A、15(60)A、20(80)、30(100)A |
|
Frequency |
50Hz |
|
Accuracy |
Class 0.5s/0.5/1.0(active);class 2.0(reactive) |
|
Power burden |
Voltage circuit: ≤2w and 5VA,Current circuit:≤2.5VA |
|
Normal operating temp. |
-20℃~+45℃ |
|
Limit operating temp. |
-30℃~+60℃ |
|
RH |
≤85% |
|
RTC accuracy(Day) |
≤0.5s(23℃) |
|
Communication protocol |
DL/T645-1997 or others required by the user |
|
Size |
278mm*164mm*78mm |
|
Weight |
About 1.9Kg |
|
|